# To cool a data center, Guangdong is looking at seawater

> Guangdong's new five-year computing plan targets a PUE below 1.2 for new large data centers by 2028 and lists six sources of cold, seawater among them, as siting rather than equipment choices.

Open the annex to Guangdong's computing plan and the seventh column lists six sources of cold. The oddest is waste heat from a nuclear plant.

On November 26 the province's data authority and its planning commission jointly issued the 15th five-year plan for computing power. The document is dated November 6.

One column inside coordinates compute and electricity. It splits cooling into three routes: nuclear, offshore wind, and a mix of energy sources. The striking part is not where the power comes from. It is where the cold comes from.

## Six kinds of cold

The list runs: absorption chilling driven by nuclear waste heat, deep cold seawater, seawater cooling, reservoir cooling, cold energy from LNG regasification, chilling from waste steam.

Two of the six use what someone else is throwing away — reactor heat, and the cold released when LNG turns back into gas. Neither needs a compressor. The other four are seawater and reservoirs.

None of this is a procurement list. It is a siting list. Seawater, reservoirs, LNG terminals and nuclear stations do not move; the cold decides where the building goes. The same column adds a plainer idea: at substations with spare land, build the data hall next to the substation. That saves metres, not degrees.

The targets attached: by 2028, over 1,000 EFlops (FP16) of intelligent compute in the province, more than 80% renewable electricity at data centers, and a PUE below 1.2 for new large facilities.

## A quarter of the bill

PUE is total power divided by compute-equipment power. At 1, every kilowatt-hour computes. Above 1, the excess goes to cooling, distribution and line losses.

As of August, the national average for compute centers was 1.34. Roughly one kilowatt-hour in four does not compute anything.

Guangdong's 1.2 applies to new large and very large facilities. Set against a 1.34 national average, the two are not strictly comparable: one is a threshold for new builds, the other an average across the existing fleet. The direction is still readable.

From 1.34 to 1.2, holding compute load constant, total power falls 10.4%, and the bill with it. Why that matters: electricity is 60% to 70% of a data center's operating cost. A tenth off the bill is 6 to 7 points off total cost. On a five-to-ten-year depreciation cycle, that is not a rounding error.

And the tenth does not come from better air conditioners. The plan's route is to turn cooling from an equipment problem into a geography problem.

One part is usually skipped: PUE counts power, not water. In a tower-cooled facility the water evaporates and carries the heat away, so the meter on the wall slows and the meter on the pipe speeds up. Swap in seawater or reservoir water and evaporation drops, and so does the power. The plan sets no water-consumption target; this column still counts electricity.

## Two sets of numbers

Two national figures have been circulating together.

The first: compute centers in China used 170 TWh in 2025, or 1.6% of all electricity consumed in the country. Divide one by the other and national consumption was about 10,600 TWh.

The second: in the first six months of 2026, internet data services used 49.4 TWh, up 44.0% year on year.

Both come from a signed Guangming Daily article on November 26 by Wang Xiaoming of the Inner Mongolia party school. The numbers are fine. They cannot be subtracted.

The 170 TWh is a facility count over a full year. The 49.4 TWh is an industry category over half a year, and "internet data services" is not the same set as "compute centers". Double the half-year figure to 98.8 TWh, compare it with 170 TWh, and you get a decline in compute power use.

That conclusion is false.

## Thirty-five fen on the grassland

In Ulanqab, Inner Mongolia, compute projects pay 0.32 to 0.38 yuan per kilowatt-hour delivered, and overall costs run 30% to 50% below first-tier eastern cities.

Five direct-renewable projects have been approved there, bundling wind, solar, storage and the data hall into one system that serves itself first. Envision's first phase is about 200 MW, handed to customers in October, with a target of 80% direct renewable supply.

200 MW at full load for a year is 1.75 TWh. At 0.35 yuan, that is 610 million yuan of electricity.

Full load is an assumption: real consumption depends on rack occupancy and load curves, neither public, so treat 610 million as an order of magnitude, not an invoice.

Ningxia's Zhongwei does it differently: China Datang built a 500 MW solar plant at its cloud base, physically supplying power in daylight and handing over to wind after dark. One place uses a market price; the other uses a wire.

## Moving the plant to the wind

Guangdong's three routes lean on geography. Huizhou's line is direct nuclear connection, written as an exploration of siting very large intelligent-compute clusters on nuclear power. Yangjiang and Huizhou also plan gigawatt-class AI compute facilities paired with energy systems. Shantou, which hosts an international submarine cable landing station, is told to explore an undersea data center.

The undersea idea has obvious appeal: seawater outside the wall, no cooling tower, short latency to coastal cities. The plan writes "explore" and stops. Nothing on maintenance, nothing on swapping parts.

If the coast competes on cold, Shaoguan in the northern hills competes on distance: 250 EFlops (FP16) by 2027, 800 by 2030, 5 milliseconds or less to major cities. For 2030 the provincial target is more than 2,500 EFlops, with 4,000 as the stretch.

Stack the ledgers: PUE from 1.34 to 1.2 saves a tenth; the price gap from coast to grassland is about 30 fen a kilowatt-hour; the renewable target on paper is 80%.

Multiply the three and you get whether a data hall survives. Siting, in the end, is decided by water temperature, wind, and the distance to a substation.